If you manage a school, you probably already suspect some of your classrooms get stuffy by mid-morning. Students get drowsy after lunch, and the same rooms draw the same complaints every term.

You're not imagining it. A Victorian study of ten classrooms across five schools recorded CO₂ levels between 912 and 2,235 ppm, with peaks of 5,000 ppm during lessons. About 80% of those classrooms fell short of the 10 to 12 litres per second per person of outdoor air that Australian Standard AS 1668.2 calls for.

The harder question is what to do about it when the capital budget is already spoken for. The US Environmental Protection Agency has spent three decades answering exactly that question, and its answer is free to download.

What the IAQ Tools for Schools kit is

The EPA launched its IAQ Tools for Schools program in 1995. The current Action Kit dates from 2014 and is still maintained. Its stated aim is to help schools improve indoor air "at little- or no-cost using straightforward activities and in-house staff."

It has four main parts:

  • IAQ Coordinator's Guide: how to appoint one person to own indoor air quality and build a management plan around them
  • IAQ Reference Guide: practical measures for preventing, diagnosing and fixing common problems, from mould and asthma triggers to portable classrooms and basic measurement equipment
  • Problem Solving Tool: pick a symptom (headaches, odours, drowsiness) and it lists the likely causes
  • 11 checklists: split by role (teachers, admin staff, school nurse, school leadership) and by function (ventilation, maintenance, renovations, food service, waste, pest management and a walk-through inspection)

The big idea is in how it's organised. It treats indoor air as something a school manages every week, not a one-off engineering project.

What carries over to Australian schools

Most of the kit's management thinking translates directly. The parts worth borrowing:

  • A named IAQ coordinator. Air quality usually falls between facilities, teaching staff and the business office. Giving one person the job closes that gap.
  • Checklists for the people in the room. Teachers notice blocked vents, closed windows and furniture pushed against supply grilles long before a maintenance contractor does. The classroom checklist turns those observations into data.
  • A written management plan. Recording who checks what, and how often, means good habits survive staff turnover.
  • Symptom-led troubleshooting. Starting from the complaint ("Room 14 gets stuffy after lunch") and working back to the cause is how most real problems get solved.
  • Folding IAQ into renovations. The renovation checklist makes sure each upgrade improves the air, rather than introducing new pollutants from paints, adhesives and flooring.

What doesn't translate, and what applies here instead

The kit was written for American buildings, codes and risks. A few sections need swapping for local equivalents.

  • Ventilation rates. EPA kit: ASHRAE standards. Australia: AS 1668.2 sets outdoor air for mechanically ventilated classrooms at 10 to 12 L/s per person.
  • Building code. EPA kit: US state and local codes. Australia: National Construction Code Part F6 covers light and ventilation, including a minimum openable window area for naturally ventilated rooms.
  • CO₂ benchmark. EPA kit: used as a ventilation indicator. Australia: The NCC's indoor air verification method uses 850 ppm (8-hour average). It's a design benchmark, not a mandatory limit for existing schools.
  • Radon. EPA kit: a major section. Australia: A minor concern in most Australian buildings.
  • Climate. EPA kit: heating-dominated buildings. Australia: Most Australian classrooms rely on opening windows, so hot days, cold mornings and bushfire smoke all push windows shut.

That last point matters most. Natural ventilation works only when the windows are open. On the days they stay closed, CO₂ climbs fast, and a checklist alone won't fix it.

As far as we're aware, Australia has no national program like Tools for Schools, and no mandatory indoor air standard for existing school buildings. Until that changes, schools are left to manage it themselves.

A Perth school already doing this

We spoke with Philip Gale, Facility Manager at All Saints' College in Perth, about how the school approaches classroom air. Much of what he described lines up with the EPA's model, without anyone working from the kit.

  • It's treated as duty of care. "Indoor air quality is important as part of our duty of care in providing appropriate safe spaces," Philip said.
  • Fresh air comes first. "Fresh air is the most important issue to address in the first instance."
  • They measure it. CO₂ monitors in classrooms show which rooms aren't getting enough outdoor air.
  • Upgrades are staged. Outside air fans went into the new science classrooms, and a building management system now monitors multiple buildings. Indoor air quality is part of the capital works program, not a separate wish list.

Philip was also candid about the hard part: "The thousands of square metres of older facilities are the issue." That's true of most schools, and it's why the low-cost, management-first approach matters.

Read the full interview with All Saints' College

Where to start

You don't need the whole kit to make progress. Five low-cost steps that combine the EPA's approach with Australian practice:

  1. Name a coordinator. Pick one person who owns indoor air quality and give them a direct line to facilities and leadership.
  2. Measure CO₂ in your worst rooms. A handful of monitors over a few weeks will show which classrooms fall short, and when.
  3. Run the classroom and ventilation checklists. Download them from the EPA, adapt them to your buildings, and have teachers and maintenance staff complete them.
  4. Fix the free things first. Unblock vents, clean or replace filters, check outside air dampers are actually open, and agree when windows should be open.
  5. Put what's left into the capital plan. Anything that needs money, like mechanical ventilation or outside air fans, goes into the works program with the data to back it.

Better air is mostly good management

The EPA kit's main lesson is that most classroom air problems are management problems before they're engineering problems. Schools that measure, assign responsibility and build fixes into the works they already plan get most of the benefit for very little cost.

QED helps schools and other building owners measure and improve indoor air quality, from baseline CO₂ assessments to ventilation reviews. QED is Australia's only NATA-accredited provider of NABERS Indoor Environment ratings.